Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2014 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/20/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLUF UNUSED OPENING IN METER ENCLOSURE. 2. INSTALL BOND BUSHING BETWEEN METER BASE AND MAIN SERVICE DISC. SW. INSTALL R-PINS FOR FUSES. 3.SUPPORT # BARE GROUND TO STRUCTURE. 4. BOND WATE AND GAS PIPING 5. J-BOXES NEED TO HAVE CONDUCTORS TERMINATED OR CAPPED OFF. 6. CONTR. TO VERIFY 2X4 LAYING LIGHT FIXTURES LISTING COMPLIES WITH INSTALLATIONS. IT MAY NOT BE PERMISSIBLE FOR LIGHT FIXTURE TO BE SECURED TO COMBUSTIBLE MATERIAL |