Permit: T12CM06251

Parcel: 118050660

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/19/2014 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/20/2013 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLUF UNUSED OPENING IN METER ENCLOSURE.
2. INSTALL BOND BUSHING BETWEEN METER BASE AND MAIN SERVICE DISC. SW. INSTALL R-PINS FOR FUSES.
3.SUPPORT # BARE GROUND TO STRUCTURE.
4. BOND WATE AND GAS PIPING
5. J-BOXES NEED TO HAVE CONDUCTORS TERMINATED OR CAPPED OFF.
6. CONTR. TO VERIFY 2X4 LAYING LIGHT FIXTURES LISTING COMPLIES WITH INSTALLATIONS. IT MAY NOT BE PERMISSIBLE FOR LIGHT FIXTURE TO BE SECURED TO COMBUSTIBLE MATERIAL