Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Apply Date:
09/06/2012
Applicant:
METRO TUCSON EXPEDITING & DEVELOPMENT
Description:
TI: FACADE REMODEL
Contractors:
  • BARKER MORRISSEY CONTRACTING INC **APA**

Permit Reviews

Permit Number - T12CM05578
Permit Status: Final
Permit Description: TI: FACADE REMODEL
Start Date Submittal Complete Date Status  
09/06/2012 PLANS OK TO SUBMIT - COMM 09/06/2012 COMPLETED Review Details
09/06/2012 COMMERCIAL - TI 09/19/2012 COMPLETED Review Details
09/19/2012 RESUBMITTAL 09/28/2012 COMPLETED Review Details
09/28/2012 RESUBMITTAL 09/28/2012 ACTIVE Review Details

Completed Inspections

Permit Status: Final
Permit Number: T12CM05578
Permit Description: TI: FACADE REMODEL
Total Completed Inspections - 21
Date Description Inspector Results Comments
11/09/2012 REINFORCED MASONRY PRE-GROUT JBURGE Approved IVRS - Inspection :*
11/09/2012 BUILDING PRE-SLAB JBURGE Approved IVRS - Inspection :*
11/09/2012 EXCAVATION/LAYOUT REBAR & ZON JBURGE Approved IVRS - Inspection :*
11/20/2012 FRAMING JBURGE Approved IVRS - Inspection :*
11/20/2012 EXT METAL CLIPS/EXT SHEATHING JBURGE Approved IVRS - Inspection :*
11/26/2012 STUCCO MESH JBURGE Approved IVRS - Inspection :*
11/29/2012 NPPO - FINAL MRUSSO Approved
11/29/2012 SIGN - FINAL MRUSSO Approved
11/29/2012 LANDSCAPE - FINAL MRUSSO Approved
11/29/2012 RIGHT OF WAY - FINAL P.Whiddon Approved
12/03/2012 STEM WALL/RETAINING WALL JBURGE Approved IVRS - Inspection :*
12/03/2012 ENGINEERING - FINAL MRUSSO Approved
12/04/2012 BUILDING - PROGRESS JBURGE Approved IVRS - Inspection :*
12/04/2012 ROOF NAILING JBURGE Approved IVRS - Inspection :*
12/04/2012 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
12/05/2012 FIRE - FINAL CSCHULTZ Approved
12/05/2012 FIRE SPKLR - FINAL CSCHULTZ Approved
12/05/2012 FIRE - FINAL CSCHULTZ Approved Replace taped and painted heads in the following areas: TV section, Recliners, dinning room tables. X10
Remove two heads next to duct work need to be 4" inches or more away by TV's and Recliners area.
In janitors closet install a ceiling or extend walls all the away to the deck or install uprights above ceiling throughout office and restrooms.
Need new cal plate.
Need a clear access to the inspectors' valve on the southwest corner wall.
Need to test the flow switch with the inspectors test valve that is buried behind the wall southwest corner.
Need lock out on breaker for alarm panel.
12/05/2012 FIRE SPKLR - FINAL CSCHULTZ Approved Replace taped and painted heads in the following areas: TV section, Recliners, dinning room tables. X10
Remove two heads next to duct work need to be 4" inches or more away by TV's and Recliners area.
In janitors closet install a ceiling or extend walls all the away to the deck or install uprights above ceiling throughout office and restrooms.
Need new cal plate.
Need a clear access to the inspectors' valve on the southwest corner wall.
Need to test the flow switch with the inspectors test valve that is buried behind the wall southwest corner.
Need lock out on breaker for alarm panel.
12/05/2012 SHEET ROCK NAILING JBURGE Approved OK PER BUILDING FINAL
12/05/2012 BUILDING ABOVE CEILING JBURGE Approved OK PER BUILDING FINAL

Documents

File Name Document Type  
001_A0.0.TIF CONSTRPLANS VIEW
002_AD.1.TIF CONSTRPLANS VIEW
003_A0.1.TIF CONSTRPLANS VIEW
004_A0.2.TIF CONSTRPLANS VIEW
005_A1.0.TIF CONSTRPLANS VIEW
006_A1.1.TIF CONSTRPLANS VIEW
007_A2.0.TIF CONSTRPLANS VIEW
008_A3.0.TIF CONSTRPLANS VIEW
009_A4.0.TIF CONSTRPLANS VIEW
010_A5.0.TIF CONSTRPLANS VIEW
011_A5.1.TIF CONSTRPLANS VIEW
012_S1.0.TIF CONSTRPLANS VIEW
013_S1.1.TIF CONSTRPLANS VIEW
014_S2.0.TIF CONSTRPLANS VIEW
015_S3.0.TIF CONSTRPLANS VIEW
016_S4.0.TIF CONSTRPLANS VIEW
017_S5.0.TIF CONSTRPLANS VIEW
018_S5.1.TIF CONSTRPLANS VIEW
019_S5.2.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW