Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM05578
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 4: THE FOOTING INDICATED IN DETAIL 05/A0.1 STILL DOES NOT MATCH DETAIL 107/S4.0. COORDINATE.
2. PREVIOUS COMMENT 9: THE REQUIRED DIMENSION FROM GRADE TO THE BOTTOM OF THE SIGN IS 7'-0" PER THE ARIZONA DEPARTMENT OF TRANSPORTATION. REVISE.
3. PREVIOUS COMMENT 15: THE DOWEL LENGTH AND MINIMUM EMBEDMENT INTO EACH SIDE OF THE CONCRETE SLAB IS NOT PROVIDED IN DETAIL 08/A4.0. REVISE.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/28/2012 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review