Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Address NEW:
1215 E PENNSYLVANIA ST
Apply Date:
07/30/2012
Applicant:
METRO TUCSON EXPEDITING & DEVELOPMENT
Description:
TI: DATA STORAGE FACILITY
Contractors:
  • RINDERKNECHT ASSOCIATES INC

Permit Reviews

Permit Number - T12CM04620
Permit Status: Final
Permit Description: TI: DATA STORAGE FACILITY
Start Date Submittal Complete Date Status  
07/30/2012 PLANS OK TO SUBMIT - COMM 07/30/2012 COMPLETED Review Details
07/30/2012 COMMERCIAL - TI 08/28/2012 COMPLETED Review Details
08/29/2012 RESUBMITTAL 08/30/2012 COMPLETED Review Details
08/30/2012 RESUBMITTAL 09/10/2012 COMPLETED Review Details

Completed Inspections

Permit Status: Final
Permit Number: T12CM04620
Permit Description: TI: DATA STORAGE FACILITY
Total Completed Inspections - 29
Date Description Inspector Results Comments
09/17/2012 ELECTRIC - UFER MRAMBER Approved UFER AND REBAR AT SAT PAD OK TO POUR
10/12/2012 PLUMBING - ABOVE CEILING BBENEDON Approved IVRS - Inspection :*
10/26/2012 MECHANICAL - HYDRONIC PIPING MRAMBER Approved IVRS - Inspection :*
11/02/2012 EXCAVATION/LAYOUT REBAR & ZON MRAMBER Approved 1) 2 PADS AT GENRATER LOCATION OK TO POUR
11/06/2012 PLUMBING - INTERMEDIATE MRAMBER Approved 1) WEST ROOMS CONDENSATE OK
2) ELEC. ROOM MAIN DUCT AND BRANCH OK
3) WATER LINES TO LEIBERTS OK
11/28/2012 ELECTRIC - UNDERGROUND DSANTACR Approved OK COMPLETE IN BLD- AT SERVICE AREA.
12/04/2012 BUILDING ABOVE CEILING MRAMBER Approved NOC ROOM OK MAN TRAP ROOM OK MECH,ELEC AND BLDG
12/04/2012 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
12/04/2012 ELECTRIC - PROGRESS MRAMBER Approved IVRS - Inspection :*
12/05/2012 ELECTRIC - INTERMEDIATE MRAMBER Approved 1. FRAMING AT HALL 164 BETWEEN C.L. 5&6 OK TO ROCK BOTH SIDES
2. ELECT INT AT HALL 164 OK BETWEEN C.L. 5 & 6
12/05/2012 FRAMING MRAMBER Approved IVRS - Inspection :*
12/06/2012 SHEET ROCK NAILING MRAMBER Approved SHEET ROCK NAILING AT HALL 164 OK
12/06/2012 MECHANICAL - ABOVE CEILING MRAMBER Approved 1. CORRIDORS SURROUNDING NOC ROOM MECH. OK
02/28/2013 TEP CLEARANCE - AM DSANTACR Approved TEC
03/08/2013 NPPO - FINAL DROBERTS Approved
03/08/2013 SIGN - FINAL DROBERTS Approved
03/08/2013 LANDSCAPE - FINAL DROBERTS Approved
03/08/2013 ENGINEERING - FINAL DROBERTS Approved
03/08/2013 PLUMBING - PROGRESS DSANTACR Approved IVRS - Inspection :*
03/08/2013 ELECTRIC - CABLE DROP DSANTACR Approved IVRS - Inspection :*
03/08/2013 PLUMBING - ROUGH, SOIL DSANTACR Approved IVRS - Inspection :*
03/14/2013 FIRE - FINAL CBASALDU Approved
04/18/2013 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
04/24/2013 RIGHT OF WAY - FINAL MCASTRO Approved
04/24/2013 PLUMBING - FINAL MRAMBER Approved IVRS - Inspection :*
07/15/2013 MECHANICAL - FINAL LHANLY Approved LETTER OF TESTING FOR DUCT DETECTORS ACCEPTED FROM FIRE ALARM CONTRACTOR.
07/15/2013 ELECTRIC - TEMP POWER FOR TEST LHANLY Approved
07/15/2013 BUILDING - PROGRESS LHANLY Approved
07/15/2013 BUILDING - FINAL LHANLY Approved LETTER OF TESTING ON SMOKE DETECTORS FROM FIRE ALARM COMPANY ACCEPTED. OK TO FINAL