Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T12CM04620
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2013 | ELECTRIC - PROGRESS | Approved | ||
03/08/2013 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
02/26/2013 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK SERVICE EQUIP, BONDING RECD TORQUE LETTER HY POT APPROVAL |
|
02/25/2013 | ELECTRIC - PROGRESS | Partial Approval | -as per last inspection notes - also need caution signage for em system -ok makeup and xformers at service equipment |
|
02/14/2013 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) TORQUE LETTER FOR GEAR, SES EQUIP. 2) HUPOT TEST RESULTS. 3) GEN TEST RESULTS |
|
12/04/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
10/05/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
10/03/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* |