Permit: T12CM03613
Permit Details
Apply Date:
06/19/2012
Applicant:
BERMUDEZ MARCO ANTONIO & GLORIA R JT/RS
Description:
RECONNECT:ELECTRIC:COMM
Outstanding Activity Conditions
Permit Number - T12CM03613
Permit Status: Final
Permit Description: RECONNECT:ELECTRIC:COMM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/19/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T12CM03613
Permit Description: RECONNECT:ELECTRIC:COMM
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2012 | ELECTRIC - RECONNECT | RHOLLAND | Approved | MISIDENTIFIED CONDUCTORS NEED TO BE RE-PULLED, CANNOT REIDENITFY WITH TAPE. USE LAY-IN LUG FOR BONDING GUTTER AND REMOVE THE #10 WHICH IS DOUBLE LUGGED IN DISCONNECT. USE PROPER FITTING FOR CONNECTING EQUIP. GROUNDING CONDUCTORS. CURRENT SPLIT BOLT IS NOT DESIGNED FOR THIS PURPOSE. |
| 07/09/2012 | TEP CLEARANCE - PM | BCOTTLE | Approved | |
| 07/09/2012 | ELECTRIC - FINAL | LHANLY | Approved | |
| 07/09/2012 | ELECTRIC - RECONNECT | LHANLY | Approved | PM RE-INSPECTION...CORRECTIONS MADE |
| 07/09/2012 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 07/09/2012 | ELECTRIC - RECONNECT | RHOLLAND | Approved | IVRS - Inspection :* |