Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
106 W DRACHMAN ST
Apply Date:
06/19/2012
Applicant:
BERMUDEZ MARCO ANTONIO & GLORIA R JT/RS
Description:
RECONNECT:ELECTRIC:COMM

Outstanding Activity Conditions

Permit Number - T12CM03613
Permit Status: Final
Permit Description: RECONNECT:ELECTRIC:COMM
Total Outstanding Activity Conditions - 1
Date Name
06/19/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T12CM03613
Permit Description: RECONNECT:ELECTRIC:COMM
Total Completed Inspections - 6
Date Description Inspector Results Comments
07/09/2012 ELECTRIC - RECONNECT RHOLLAND Approved MISIDENTIFIED CONDUCTORS NEED TO BE RE-PULLED, CANNOT REIDENITFY WITH TAPE.

USE LAY-IN LUG FOR BONDING GUTTER AND REMOVE THE #10 WHICH IS DOUBLE LUGGED IN DISCONNECT.

USE PROPER FITTING FOR CONNECTING EQUIP. GROUNDING CONDUCTORS. CURRENT SPLIT BOLT IS NOT DESIGNED FOR THIS PURPOSE.
07/09/2012 TEP CLEARANCE - PM BCOTTLE Approved
07/09/2012 ELECTRIC - FINAL LHANLY Approved
07/09/2012 ELECTRIC - RECONNECT LHANLY Approved PM RE-INSPECTION...CORRECTIONS MADE
07/09/2012 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
07/09/2012 ELECTRIC - RECONNECT RHOLLAND Approved IVRS - Inspection :*

Documents

File Name Document Type  
None DOCUMENTS VIEW