Description:
INSTALL:ROOF TOP A/C UNIT:WATER HEATER:RES T12DV02401

Permit Reviews

Permit Number - T12CM02129
Permit Status: Final
Permit Description: INSTALL:ROOF TOP A/C UNIT:WATER HEATER:RES T12DV02401
Start Date Submittal Complete Date Status  
04/23/2012 OTHER 04/23/2012 ACTIVE Review Details

Outstanding Activity Conditions

Permit Number - T12CM02129
Permit Status: Final
Permit Description: INSTALL:ROOF TOP A/C UNIT:WATER HEATER:RES T12DV02401
Total Outstanding Activity Conditions - 1
Date Name
04/23/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T12CM02129
Permit Description: INSTALL:ROOF TOP A/C UNIT:WATER HEATER:RES T12DV02401
Total Completed Inspections - 3
Date Description Inspector Results Comments
11/19/2012 MECHANICAL - FINAL MRAMBER Approved 1. ACCEPTABLE MATERIAL FOR T & P DRAIN C.P.V.C,COPPER, GALVANIZED PIPE
2. B-VENT ON WATER HEATER IS UPSIDE DOWN, NOT VENTING CORRECLTY REINSTALL CORRECTLY
3. T-STAT WIRE IS TO BE RUN IN CONDUIT (SEALTITE) ELEC SEAL TITE IS TO BE BLOCKED UP AND OF ROOF 1 1/2
4. DUCT SEALER NOT TO BE USED AS ROF REPAIR ALL ROOF TRATIONS ARE TO HAVE ROOD JACKS
5. ALL ROOF TOP DUCT TO HAVE 2" DUCTLINER 1/2" NOT ACCEPTABLE
6. CONDENSATE NOT INSTALLED CNDENSATE TO BE TERMINATED IN AN APPROVED MANNER 6" ABOVE GRADE
7. GAS PUPE AT ROOF TOP UNIT NOT PROPERLY SUPPORTED
11/19/2012 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
11/19/2012 PLUMBING - FINAL MRAMBER Approved IVRS - Inspection :*