Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2013 | MECHANICAL - FINAL | Approved | ||
| 06/19/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/19/2013 | MECHANICAL - FINAL | Denied | - SEE NOTES # LAST INSP FOR AC UNIT - WATER HTR OK |
|
| 11/19/2012 | MECHANICAL - FINAL | Not ready for Inspection | 1. ACCEPTABLE MATERIAL FOR T & P DRAIN C.P.V.C,COPPER, GALVANIZED PIPE 2. B-VENT ON WATER HEATER IS UPSIDE DOWN, NOT VENTING CORRECLTY REINSTALL CORRECTLY 3. T-STAT WIRE IS TO BE RUN IN CONDUIT (SEALTITE) ELEC SEAL TITE IS TO BE BLOCKED UP AND OF ROOF 1 1/2 4. DUCT SEALER NOT TO BE USED AS ROF REPAIR ALL ROOF TRATIONS ARE TO HAVE ROOD JACKS 5. ALL ROOF TOP DUCT TO HAVE 2" DUCTLINER 1/2" NOT ACCEPTABLE 6. CONDENSATE NOT INSTALLED CNDENSATE TO BE TERMINATED IN AN APPROVED MANNER 6" ABOVE GRADE 7. GAS PUPE AT ROOF TOP UNIT NOT PROPERLY SUPPORTED |
|
| 04/25/2012 | MECHANICAL - FINAL | Not ready for Inspection | 1 - REQUIRE ACCESSIBLE SHUT OFF AT COLD INLET. MAY NOT COMBINE FLEX CONNECTORS, BLACK IRON PIPE NOT APPROVED FOR T&P RELIEF DRAIN. 2 - PROVIDE LADDER FOR ROOF ACCESS |