Description:
REPLACE WATER SOURCE HEAT PUMS WITH SPLIT SYSTEM HEAT PUMPS - COMM

Permit Reviews

Permit Number - T12CM00909
Permit Status: Expired
Permit Description: REPLACE WATER SOURCE HEAT PUMS WITH SPLIT SYSTEM HEAT PUMPS - COMM
Start Date Submittal Complete Date Status  
03/07/2012 OTHER 04/03/2012 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T12CM00909
Permit Status: Expired
Permit Description: REPLACE WATER SOURCE HEAT PUMS WITH SPLIT SYSTEM HEAT PUMPS - COMM
Total Outstanding Activity Conditions - 1
Date Name
03/07/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T12CM00909
Permite Description: REPLACE WATER SOURCE HEAT PUMS WITH SPLIT SYSTEM HEAT PUMPS - COMM
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
ELECTRIC - INTERMEDIATE N/A Not Inspected
ELECTRIC - ABOVE CEILING N/A Not Inspected
ELECTRIC - FINAL N/A Not Inspected
MECHANICAL - ABOVE CEILING N/A Not Inspected
06/13/2012 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection :*
PROVIDE FILTERS IN FAN COILS
PROVIDE ACCESS TO DISCONNECT
LABEL FROM COILS AND CONDENSORS
PROVIDE A PROTECTIVE COATING ON EXPOSED ARMFLEX
DO NOT USE DUCT TAPE OUTDOORS
USE UV RATED ZIP TIES BLACK
3 1/2 TPM CONDENSOR NOT FUSED CORRECTLY
PLANS CALL FOR SPRING INSOLATOR AT FAN COILS
INSULATION IN ROOF CURBS SIGHT GLASS AT CONDENSORS
INSULATED CONDENSATE. PROVIDE A LETTER FROM ENGINEER TO CHANGE ANY REQUIREMENTS ON PLANS. PLANS ALSO REQUIRE THICK ARMFLEX AND COATED WITH ALUMINUM JACKET OUTDOORS