Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T12CM00909
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE FILTERS IN FAN COILS PROVIDE ACCESS TO DISCONNECT LABEL FROM COILS AND CONDENSORS PROVIDE A PROTECTIVE COATING ON EXPOSED ARMFLEX DO NOT USE DUCT TAPE OUTDOORS USE UV RATED ZIP TIES BLACK 3 1/2 TPM CONDENSOR NOT FUSED CORRECTLY PLANS CALL FOR SPRING INSOLATOR AT FAN COILS INSULATION IN ROOF CURBS SIGHT GLASS AT CONDENSORS INSULATED CONDENSATE. PROVIDE A LETTER FROM ENGINEER TO CHANGE ANY REQUIREMENTS ON PLANS. PLANS ALSO REQUIRE THICK ARMFLEX AND COATED WITH ALUMINUM JACKET OUTDOORS |