Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
5530 E BROADWAY BL
Apply Date:
10/09/2012
Applicant:
CUTLER FIRE PROTECTION INC ,
Description:
Add 262, relocate 12 fire sprinklers
Contractors:
  • CUTLER FIRE PROTECTION INC ,

Outstanding Activity Conditions

Permit Number - T12BU01198
Permit Status: Final
Permit Description: Add 262, relocate 12 fire sprinklers
Total Outstanding Activity Conditions - 1
Date Name
10/09/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T12BU01198
Permit Description: Add 262, relocate 12 fire sprinklers
Total Completed Inspections - 2
Date Description Inspector Results Comments
12/05/2012 FIRE SPKLR - FINAL CSCHULTZ Approved
12/05/2012 FIRE SPKLR - FINAL CSCHULTZ Approved Replace taped and painted heads in the following areas: TV section, Recliners, dinning room tables. X10
Remove two heads next to duct work need to be 4" inches or more away by TV's and Recliners area.
In janitors closet install a ceiling or extend walls all the away to the deck or install uprights above ceiling throughout office and restrooms.
Need new cal plate.
Need a clear access to the inspectors valve on the southwest corner wall.