Inspection Status: Denied
Inspection History: FIRE SPKLR - FINAL
Permit Number - T12BU01198
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/05/2012 | FIRE SPKLR - FINAL | Denied | Replace taped and painted heads in the following areas: TV section, Recliners, dinning room tables. X10 Remove two heads next to duct work need to be 4" inches or more away by TV's and Recliners area. In janitors closet install a ceiling or extend walls all the away to the deck or install uprights above ceiling throughout office and restrooms. Need new cal plate. Need a clear access to the inspectors valve on the southwest corner wall. |
|
12/05/2012 | FIRE SPKLR - FINAL | Approved |