Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Address:
601 W 22ND ST
Address NEW:
601 W 22ND ST
Apply Date:
08/28/2012
Applicant:
A F P FIRE PROTECTION L L C
Description:
Install 885 new fire sprinklers with fire pump
Contractors:
  • A F P FIRE PROTECTION L L C

Outstanding Activity Conditions

Permit Number - T12BU01014
Permit Status: Closed
Permit Description: Install 885 new fire sprinklers with fire pump
Total Outstanding Activity Conditions - 1
Date Name
08/28/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Closed
Permit Number: T12BU01014
Permit Description: Install 885 new fire sprinklers with fire pump
Total Completed Inspections - 2
Date Description Inspector Results Comments
11/01/2012 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved 200 PSI FOR 2 HOURS AND PLACEMENT APPROVED THIS IS ALSO PIPING TO FIRE PUMP AND FIRE PUMP.
11/05/2012 FIRE SPKLR - FINAL CSCHULTZ Approved Need jocky pump install or chang plans removing pump from system.
Need tampers on outside OS&Y's.
Brace inspectors test valve for canopy area.
Brace all 2 1/2" hose connections
Install inspector test valve for riser #1 by battery station
Install riser room sign on riser door

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
002_SPRINKLER.TIF FIRE PLANS VIEW
003_SPRINKLER.TIF FIRE PLANS VIEW
004_SPRINKLER.TIF FIRE PLANS VIEW
005_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW