Permit: T12BU01014
Permit Details
Apply Date:
08/28/2012
Applicant:
A F P FIRE PROTECTION L L C
Description:
Install 885 new fire sprinklers with fire pump
Contractors:
- A F P FIRE PROTECTION L L C
Outstanding Activity Conditions
Permit Number - T12BU01014
Permit Status: Closed
Permit Description: Install 885 new fire sprinklers with fire pump
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/28/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Closed
Permit Number: T12BU01014
Permit Description: Install 885 new fire sprinklers with fire pump
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2012 | FIRE SPKLR - OH PIPING & HYDRO | CSCHULTZ | Approved | 200 PSI FOR 2 HOURS AND PLACEMENT APPROVED THIS IS ALSO PIPING TO FIRE PUMP AND FIRE PUMP. |
| 11/05/2012 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | Need jocky pump install or chang plans removing pump from system. Need tampers on outside OS&Y's. Brace inspectors test valve for canopy area. Brace all 2 1/2" hose connections Install inspector test valve for riser #1 by battery station Install riser room sign on riser door |