Inspection History Details
Inspection Status: Closed
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2022 | FIRE SPKLR - FINAL | Closed | CONTRACTOR DID NOT CALL IN PERMIT TO COMPLETE FINAL | |
| 11/05/2012 | FIRE SPKLR - FINAL | Denied | Need jocky pump install or chang plans removing pump from system. Need tampers on outside OS&Y's. Brace inspectors test valve for canopy area. Brace all 2 1/2" hose connections Install inspector test valve for riser #1 by battery station Install riser room sign on riser door |
|
| 11/01/2012 | FIRE SPKLR - FINAL | Denied | Remove soffit in southwest corner of cooler area. No storage above 12' until fire pump acceptance test is done and passed. |