Permit: T12BU01014

Parcel: 11808002T


Addresses:

601 W 22ND ST

Inspection Status: Closed

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
10/07/2022 FIRE SPKLR - FINAL Closed CONTRACTOR DID NOT CALL IN PERMIT TO COMPLETE FINAL
11/05/2012 FIRE SPKLR - FINAL Denied Need jocky pump install or chang plans removing pump from system.
Need tampers on outside OS&Y's.
Brace inspectors test valve for canopy area.
Brace all 2 1/2" hose connections
Install inspector test valve for riser #1 by battery station
Install riser room sign on riser door
11/01/2012 FIRE SPKLR - FINAL Denied Remove soffit in southwest corner of cooler area.
No storage above 12' until fire pump acceptance test is done and passed.