Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
7600 E BROADWAY BL
Apply Date:
08/01/2012
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
  • SIMPLEX GRINNELL L P

Outstanding Activity Conditions

Permit Number - T12BU00921
Permit Status: Expired
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date Name
08/01/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T12BU00921
Permite Description: FIRE ALARM
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
09/17/2012 FIRE - ALARM FINAL N/A Denied 1. Need lock out on breaker for FACP
2. Need smoke install above the FACP and trans-sponder
3. Exhaust fans on the roof failed to activate when the fire alarm system was tripped, need to repair the system to proper operations.
4. Floor 6 east tamper and flow failed
5. Floor 4 east tamper and flow failed
6. Floor 1 east tamper came in as earth ground fault.
7. Need to test exhaust hood system in kitchen