Permit: T12BU00921

Parcel: 134270010


Addresses:

7600 E BROADWAY BL

Inspection Status: Denied

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
09/17/2012 FIRE - ALARM FINAL Denied 1. Need lock out on breaker for FACP
2. Need smoke install above the FACP and trans-sponder
3. Exhaust fans on the roof failed to activate when the fire alarm system was tripped, need to repair the system to proper operations.
4. Floor 6 east tamper and flow failed
5. Floor 4 east tamper and flow failed
6. Floor 1 east tamper came in as earth ground fault.
7. Need to test exhaust hood system in kitchen