Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - ALARM FINAL
Permit Number - T12BU00921
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2012 | FIRE - ALARM FINAL | Denied | 1. Need lock out on breaker for FACP 2. Need smoke install above the FACP and trans-sponder 3. Exhaust fans on the roof failed to activate when the fire alarm system was tripped, need to repair the system to proper operations. 4. Floor 6 east tamper and flow failed 5. Floor 4 east tamper and flow failed 6. Floor 1 east tamper came in as earth ground fault. 7. Need to test exhaust hood system in kitchen |