Permit: T12BU00921
Permit Details
Apply Date:
08/01/2012
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
- SIMPLEX GRINNELL L P
Outstanding Activity Conditions
Permit Number - T12BU00921
Permit Status: Expired
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/01/2012 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T12BU00921
Permite Description: FIRE ALARM
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2012 | FIRE - ALARM FINAL | N/A | Denied | 1. Need lock out on breaker for FACP 2. Need smoke install above the FACP and trans-sponder 3. Exhaust fans on the roof failed to activate when the fire alarm system was tripped, need to repair the system to proper operations. 4. Floor 6 east tamper and flow failed 5. Floor 4 east tamper and flow failed 6. Floor 1 east tamper came in as earth ground fault. 7. Need to test exhaust hood system in kitchen |