Permit: T11PL01851
Permit Details
Apply Date:
11/08/2011
Applicant:
RICE PLUMBING B*
Description:
REPAIR: GAS LEAK
Contractors:
- RICE PLUMBING COMPANY *C*
Outstanding Activity Conditions
Permit Number - T11PL01851
Permit Status: Final
Permit Description: REPAIR: GAS LEAK
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
11/08/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T11PL01851
Permit Description: REPAIR: GAS LEAK
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2011 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* PLUMBERS NOTE: 1) YOU CANNOT TEST MEDIUM PRESSURE WITH A #60 GAUGE. USE 100 POUND GAUGE IN ONE POUND INCREMENTATION IN THE FUTURE. LOW PRESSURE TEST IS 15 POUND IN 1/10 POUND INCREMENTATION 2) REPLACE MEDIUM PRESSURE REGULATOR WITH NDW REGULATOR WITH LIMITING DEVICE 3) PRESSURE TEST OK 4) LEFT GAS CARD |
11/22/2011 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
11/23/2011 | PERMIT FINALED | JWEATHER | Approved |