11/22/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
PLUMBERS NOTE:
1) YOU CANNOT TEST MEDIUM PRESSURE WITH A #60 GAUGE. USE 100 POUND GAUGE IN ONE POUND INCREMENTATION IN THE FUTURE. LOW PRESSURE TEST IS 15 POUND IN 1/10 POUND INCREMENTATION
2) REPLACE MEDIUM PRESSURE REGULATOR WITH NDW REGULATOR WITH LIMITING DEVICE
3) PRESSURE TEST OK
4) LEFT GAS CARD
11/09/2011 PLUMBING - FINAL Denied 1) WHAT IS EXTENT OF WORK ? WHERE IS REPAIR ? REQUIRE SAFE ACCESS TO ROOF
2) IF THIS IS A MEDIUM PRESSURE SYSTEM TEST PRESSURE 60 POUNDS. DO NOT TEST THRU REGULATORS OR APPLIANCES