Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
08/01/2011
Applicant:
HALL TJ
Description:
REMOVE AND REPLACE 3 TON GAS SPLIT, GROUND LEVEL
Contractors:
  • A R S AMERICAN RESIDENTIAL SERVICES LLC *

Outstanding Activity Conditions

Permit Number - T11ME00211
Permit Status: Expired
Permit Description: REMOVE AND REPLACE 3 TON GAS SPLIT, GROUND LEVEL
Total Outstanding Activity Conditions - 1
Date Name
08/01/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T11ME00211
Permite Description: REMOVE AND REPLACE 3 TON GAS SPLIT, GROUND LEVEL
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
08/17/2011 MECHANICAL - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/17/2011 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCONNECT NOT PROPERLY MOUNTED
2) DO NOT LAND 2 WIRES ON A SINGLE LUG (SURGE PROTECTOR)
3) ALL ELECTRIC WIRING PENETRATING CABINET MUST HAVE AN APPROVED TIGHTLY FASTENED CLAMP
4) PROVIDE MINIMUM 6" CLEARANCE TO COMBUSTIBLES AT FLUE PIPE
5) PROVID GASKET AT RETURN AIR OPENING
6) CONDENSATE CANNOT TERMINATE AT A WASTE VENT