Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T11EL02661
Permit Details
Apply Date:
10/11/2011
Applicant:
CITY OF TUCSON FACILTIES MANAGEMENT
Description:
POWER FOR TUCSON MEET YOURSELF
Outstanding Activity Conditions
Permit Number - T11EL02661
Permit Status: Expired
Permit Description: POWER FOR TUCSON MEET YOURSELF
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/11/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T11EL02661
Permite Description: POWER FOR TUCSON MEET YOURSELF
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
ELECTRIC - INTERMEDIATE | N/A | Not Inspected | ||
10/14/2011 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) TIGHTEN LOOSE CONDUCTOR TERMINATIONS 2) FILL UNUSED OPENINGS 3) PROVIDE CONDUCTOR STRAIN RELIEF 4) DO NOT STACK LUGS 5) SHEET METAL THREAD SCREW NOT ALLOWED FOR GROUNDING 6) DO NOT TRIM CONDUCTORS 7) LUGS NOT LISTED FOR ? STRANDED CONDUCTORS-USE LISTED ADAPTORS 8) IDENTIFY CIRCUITS 9) OK AFTER CORRECTIONS, DISCUSED WITH CITY ELECTRICIANS |