Permit: T11EL02661

Parcel: 117200100


Addresses:

165 W ALAMEDA ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/14/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) TIGHTEN LOOSE CONDUCTOR TERMINATIONS
2) FILL UNUSED OPENINGS
3) PROVIDE CONDUCTOR STRAIN RELIEF
4) DO NOT STACK LUGS
5) SHEET METAL THREAD SCREW NOT ALLOWED FOR GROUNDING
6) DO NOT TRIM CONDUCTORS
7) LUGS NOT LISTED FOR ? STRANDED CONDUCTORS-USE LISTED ADAPTORS
8) IDENTIFY CIRCUITS
9) OK AFTER CORRECTIONS, DISCUSED WITH CITY ELECTRICIANS