Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T11EL02661
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) TIGHTEN LOOSE CONDUCTOR TERMINATIONS 2) FILL UNUSED OPENINGS 3) PROVIDE CONDUCTOR STRAIN RELIEF 4) DO NOT STACK LUGS 5) SHEET METAL THREAD SCREW NOT ALLOWED FOR GROUNDING 6) DO NOT TRIM CONDUCTORS 7) LUGS NOT LISTED FOR ? STRANDED CONDUCTORS-USE LISTED ADAPTORS 8) IDENTIFY CIRCUITS 9) OK AFTER CORRECTIONS, DISCUSED WITH CITY ELECTRICIANS |