Permit: T11EL02518
Permit Details
Apply Date:
09/23/2011
Applicant:
LANCE, GEORGE GERARD
Description:
SITE ELECTRIC
Architects:
- LANCE, GEORGE GERARD
Contractors:
- DWELLINGS ,
Permit Reviews
Permit Number - T11EL02518
Permit Status: Expired
Permit Description: SITE ELECTRIC
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/15/2012 | ELECTRICAL | 02/15/2012 | COMPLETED |
| 09/23/2011 | ELECTRICAL | 09/23/2011 | COMPLETED |
| 09/23/2011 | ELECTRICAL | 02/15/2012 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T11EL02518
Permit Status: Expired
Permit Description: SITE ELECTRIC
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/23/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T11EL02518
Permite Description: SITE ELECTRIC
Total Outstanding Inspections - 6
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - INTERMEDIATE | N/A | Not Inspected | ||
| ELECTRIC - ABOVE CEILING | N/A | Not Inspected | ||
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected | ||
| 05/01/2012 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANEL "A" ON PLANS TO BE 22K ON SITE IS 10K 2) CANNOT FORK CONDUCTORS PANEL A NEUTRAL 3) BREAKERS INSTALLED DO NOT MATCH PLANS PANEL SCHEDULE 4) CANNOT LOCATE PANEL "X" PANEL ON SOUTHWEST CORNER, IF "X" THE BREAKERS & LOADS ARE NOT PER PLANS, ALSO PROTECT CONDUCTOR (NOTE #2 ON 2/27/12) AND MISSING LOCK NUTS 5) CANNOT LOCATE OTHER PANELS-NEED LABELING (B + C FOR RESTAURANT) |
| 11/09/2011 | ELECTRIC - UFER | N/A | Partial Approval | IVRS - Inspection :* 1) OK 3/0 TO GROUND RODS |
| 11/16/2011 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* 1) OK ENCASED PVC CONDUITS 2) PRIMARY BY TEP TO BE INSPECTED BY TEP |
Completed Inspections
Permit Status: Expired
Permit Number: T11EL02518
Permit Description: SITE ELECTRIC
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/29/2012 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED PER R. HOLLANDER |