Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANEL "A" ON PLANS TO BE 22K ON SITE IS 10K 2) CANNOT FORK CONDUCTORS PANEL A NEUTRAL 3) BREAKERS INSTALLED DO NOT MATCH PLANS PANEL SCHEDULE 4) CANNOT LOCATE PANEL "X" PANEL ON SOUTHWEST CORNER, IF "X" THE BREAKERS & LOADS ARE NOT PER PLANS, ALSO PROTECT CONDUCTOR (NOTE #2 ON 2/27/12) AND MISSING LOCK NUTS 5) CANNOT LOCATE OTHER PANELS-NEED LABELING (B + C FOR RESTAURANT) |
|
| 02/28/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #1 FROM PREVIOUS INSPECTION |
|
| 02/27/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ONLY 1 CONDUCTOR PER LUG 2) PROTECT CONDUCTORS 300.4 & 352.46 3) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 4) LABEL EQUIPMENT 5) SEPERATE STRUCTURES REQUIRE DISCONNECTING MEANS 225.32 OR DOCUMENTATION PER EXCEPTION #1 |
|
| 01/20/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BONDING AT SERVICE PER 250.104 2) PLAN NEEDS TO BE REVISED FOR SERVICE EQUIPMENT |