Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
7565 E 29TH ST
Address NEW:
7565 E 29TH ST
Apply Date:
09/20/2011
Applicant:
N/A
Description:
RECONNECT ELECTRIC; RES R1- UPGRADE TO 200 AMP
Contractors:
  • DUFFY ELECTRICAL INC *APA*

Outstanding Activity Conditions

Permit Number - T11EL02485
Permit Status: Final
Permit Description: RECONNECT ELECTRIC; RES R1- UPGRADE TO 200 AMP
Total Outstanding Activity Conditions - 1
Date Name
09/20/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T11EL02485
Permit Description: RECONNECT ELECTRIC; RES R1- UPGRADE TO 200 AMP
Total Completed Inspections - 5
Date Description Inspector Results Comments
11/23/2011 ELECTRIC - FINAL WLAHR Approved 1. SERVICE APPEARS TO HAVE BEEN RELOCATED - BY THE APPEARANCE OF OVERHEAD FEEDER CONNECTION.
2. SERVICE UPGRADE/RELOCATE PERMIT NEEDED.
3. ANY QUESTIONS CALL RAY MAJUTA AT 909-4891
4. NO ACCESS TO DETACHED GARAGE
5. BLANK SPACERS NEEDED AT OPEN KNOCK OUTS AT SUB-PANEL DEAD FRONT
6. BUSHING NEEDED AT BACK OF SUB PANEL AROUND HOME RUNS LOAD CONNECTORS.
7. DOUBLE CONDUCTOR UNDER SINGLE BREAKER AT SUB-PANEL
8. GROUNDS & NEUTRALS NEED TO BE SEPARATED AT SUB-PANEL
9. TOO MANY NON-CODE COMPLIANCE ITEMS TO LIST.
10. CONTACT LICENSED ELECTRICAL CONTRACTOR TO BRING UP TO CODE.
11/23/2011 ELECTRIC - RECONNECT WLAHR Approved IVRS - Inspection :
See detailed listing on site.| 999*
01/20/2012 ELECTRIC - SERVICE UPGRADE MRAMBER Approved
01/23/2012 TEP CLEARANCE - AM JWEATHER Approved RECN CLEARED PER M. RAMBER
01/23/2012 PERMIT FINALED JWEATHER Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW