Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T11EL01835
Permit Details
Apply Date:
07/08/2011
Applicant:
VITTOUSSETHEA CHHUN
Description:
RECONNECT:ELECTRIC DONUT SHOP
Outstanding Activity Conditions
Permit Number - T11EL01835
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC DONUT SHOP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/08/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T11EL01835
Permite Description: RECONNECT:ELECTRIC DONUT SHOP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2011 | ELECTRIC - RECONNECT | N/A | Partial Approval | IVRS - Inspection :* |
| 07/11/2011 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) BRING CEILING RECEPT FLUSH AND USE ARC SHIELD 2) FILL UNUSED OPENING IN JUNCTION BOX AND PANEL COVER 3) 'C' PHASE AT MAIN DISCONNECT HAS CROSSOVER AT LUG CLEAN AND RE-TIGHTEN 4) SUB PANEL HAS 120V BREAKER OR HIGH LEG 5) LABEL PANEL FOR HIGH LEG |
Completed Inspections
Permit Status: Expired
Permit Number: T11EL01835
Permit Description: RECONNECT:ELECTRIC DONUT SHOP
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2011 | TEP CLEARANCE - AM | JWEATHER | Approved | RECN CLEARED PER R. HOLLANDER |