Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T11EL01835
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BRING CEILING RECEPT FLUSH AND USE ARC SHIELD 2) FILL UNUSED OPENING IN JUNCTION BOX AND PANEL COVER 3) 'C' PHASE AT MAIN DISCONNECT HAS CROSSOVER AT LUG CLEAN AND RE-TIGHTEN 4) SUB PANEL HAS 120V BREAKER OR HIGH LEG 5) LABEL PANEL FOR HIGH LEG |