Permit: T11CM03548
Permit Details
Apply Date:
11/15/2011
Applicant:
WALT EWER
Description:
NEW HVAC SYSTEM; HOMELESS SHELTER
Contractors:
- MOUNTAIN AIRE REFR & AIR COND
Permit Reviews
Permit Number - T11CM03548
Permit Status: Expired
Permit Description: NEW HVAC SYSTEM; HOMELESS SHELTER
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/15/2011 | OTHER | 11/15/2011 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T11CM03548
Permit Status: Expired
Permit Description: NEW HVAC SYSTEM; HOMELESS SHELTER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/15/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T11CM03548
Permite Description: NEW HVAC SYSTEM; HOMELESS SHELTER
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2011 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) THERE ARE 2 SETS OF "TWINGED" UNITS 2) THE TWINGED SYSEM EXCEEDS THE 2000 CFM AIR FLOW WHICH REQUIRES DUCT SMOKE DETECTORS 3) DUCT SMOKE DETECTORS MUST BE INSTALLED IN THE RETURN SYSTEM 4) AN AUDIO/VISUAL ALARM MUST BE INSTALLED IN A CENTRALLY MONITORED LOCATION |