Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
3314 S 16TH AV
Address NEW:
3314 S 16TH AV
Apply Date:
11/15/2011
Applicant:
WALT EWER
Description:
NEW HVAC SYSTEM; HOMELESS SHELTER
Contractors:
  • MOUNTAIN AIRE REFR & AIR COND

Permit Reviews

Permit Number - T11CM03548
Permit Status: Expired
Permit Description: NEW HVAC SYSTEM; HOMELESS SHELTER
Start Date Submittal Complete Date Status  
11/15/2011 OTHER 11/15/2011 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T11CM03548
Permit Status: Expired
Permit Description: NEW HVAC SYSTEM; HOMELESS SHELTER
Total Outstanding Activity Conditions - 1
Date Name
11/15/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T11CM03548
Permite Description: NEW HVAC SYSTEM; HOMELESS SHELTER
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/02/2011 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection :*
1) THERE ARE 2 SETS OF "TWINGED" UNITS
2) THE TWINGED SYSEM EXCEEDS THE 2000 CFM AIR FLOW WHICH REQUIRES DUCT SMOKE DETECTORS
3) DUCT SMOKE DETECTORS MUST BE INSTALLED IN THE RETURN SYSTEM
4) AN AUDIO/VISUAL ALARM MUST BE INSTALLED IN A CENTRALLY MONITORED LOCATION

Documents

File Name Document Type  
None DOCUMENTS VIEW