Permit: T11CM03548

Parcel: 11918002B


Addresses:

3314 S 16TH AV

Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/04/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PHONED WALT'S NUMBER TWICE AND NO ANSWER
12/02/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) THERE ARE 2 SETS OF "TWINGED" UNITS
2) THE TWINGED SYSEM EXCEEDS THE 2000 CFM AIR FLOW WHICH REQUIRES DUCT SMOKE DETECTORS
3) DUCT SMOKE DETECTORS MUST BE INSTALLED IN THE RETURN SYSTEM
4) AN AUDIO/VISUAL ALARM MUST BE INSTALLED IN A CENTRALLY MONITORED LOCATION