Permit: T11CM03278
Permit Details
Apply Date:
10/17/2011
Applicant:
LORI SOURS
Description:
TI: OFFICE
Contractors:
- 4 L CONSTRUCTION INC ,
Permit Reviews
Permit Number - T11CM03278
Permit Status: Expired
Permit Description: TI: OFFICE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/06/2012 | REVISION - - 1ST | 01/06/2012 | COMPLETED |
| 10/17/2011 | COMMERCIAL - TI | 10/19/2011 | COMPLETED |
| 10/19/2011 | OTHER | 01/06/2012 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T11CM03278
Permit Status: Expired
Permit Description: TI: OFFICE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/17/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T11CM03278
Permite Description: TI: OFFICE
Total Outstanding Inspections - 11
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| PLUMBING - GAS PRESSURE TEST | N/A | Not Inspected | ||
| PLUMBING - GAS PRESS TEST FNL | N/A | Not Inspected | ||
| PLUMBING - FINAL | N/A | Not Inspected | ||
| MECHANICAL - ABOVE CEILING | N/A | Not Inspected | ||
| FIRE SPKLR - FINAL | N/A | Not Inspected | ||
| 04/19/2012 | BUILDING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 04/19/2012 | ELECTRIC - ABOVE CEILING | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT UDV CABLEING 725.8, 800.24, 300.11 2. FILL UNUSED OPENING IN BOXES 110.12 3. USE APPROVED METHODS TO SUPPORT M/C CABLES 330.17 + 330.30, 300.11 4. SECURLY ATTACH FIXTURES TO GRID - IF MANUFACTURES 410.16 CLIPS ARE USED THEY MUST BE EFFECTIVE 5. BOXES MORE THAN 1/4 " 314.20 + OR 1/8 " 314.21 6. WHERE ARE NEW RECEPTACLES AS PER PLANS 7. LABEL CIRCUIT DIRECTORY (408.4) + OUTSIDE COVER 8. FINISH PHASE CONDUCTOR IDENTIFICATION 9. EM LIGHTS NOT WORKING 10. NEW RECEPTACLE BOX OUTSIDE DOOR OVER FILLED |
| 04/19/2012 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT UDV CABLEING 725.8, 800.24, 300.11 2. FILL UNUSED OPENING IN BOXES 110.12 3. USE APPROVED METHODS TO SUPPORT M/C CABLES 330.17 + 330.30, 300.11 4. SECURLY ATTACH FIXTURES TO GRID - IF MANUFACTURES 410.16 CLIPS ARE USED THEY MUST BE EFFECTIVE 5. BOXES MORE THAN 1/4 " 314.20 + OR 1/8 " 314.21 6. WHERE ARE NEW RECEPTACLES AS PER PLANS 7. LABEL CIRCUIT DIRECTORY (408.4) + OUTSIDE COVER 8. FINISH PHASE CONDUCTOR IDENTIFICATION 9. EM LIGHTS NOT WORKING 10. NEW RECEPTACLE BOX OUTSIDE DOOR OVER FILLED |
| 04/19/2012 | MECHANICAL - INTERMEDIATE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 04/19/2012 | MECHANICAL - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 11/18/2011 | ELECTRIC - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection :* 1) OK WALLS 2) DISCUSSED SERVICE MODIFICATIONS WITH CONTR. TELE/DATA TERM CABINET AND HOSE BIB IN DEDICATED SPACE FOR SERVICE EQUIPMENT MUST BE RELOCATED PER 110.26 NEC |
Completed Inspections
Permit Status: Expired
Permit Number: T11CM03278
Permit Description: TI: OFFICE
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2011 | FRAMING | MHENSON | Approved | IVRS - Inspection :* |
| 11/30/2011 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* 1) SHEETROCK OK |