Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
1110 S PARK AV
Address NEW:
1110 S PARK AV
Apply Date:
10/17/2011
Applicant:
LORI SOURS
Description:
TI: OFFICE
Contractors:
  • 4 L CONSTRUCTION INC ,

Permit Reviews

Permit Number - T11CM03278
Permit Status: Expired
Permit Description: TI: OFFICE
Start Date Submittal Complete Date Status  
01/06/2012 REVISION - - 1ST 01/06/2012 COMPLETED Review Details
10/17/2011 COMMERCIAL - TI 10/19/2011 COMPLETED Review Details
10/19/2011 OTHER 01/06/2012 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T11CM03278
Permit Status: Expired
Permit Description: TI: OFFICE
Total Outstanding Activity Conditions - 1
Date Name
10/17/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T11CM03278
Permite Description: TI: OFFICE
Total Outstanding Inspections - 11
Last Inspection Date Description Inspector Results Comments
PLUMBING - GAS PRESSURE TEST N/A Not Inspected
PLUMBING - GAS PRESS TEST FNL N/A Not Inspected
PLUMBING - FINAL N/A Not Inspected
MECHANICAL - ABOVE CEILING N/A Not Inspected
FIRE SPKLR - FINAL N/A Not Inspected
04/19/2012 BUILDING - FINAL N/A Not ready for Inspection IVRS - Inspection :*
04/19/2012 ELECTRIC - ABOVE CEILING N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT UDV CABLEING 725.8, 800.24, 300.11
2. FILL UNUSED OPENING IN BOXES 110.12
3. USE APPROVED METHODS TO SUPPORT M/C CABLES 330.17 + 330.30, 300.11
4. SECURLY ATTACH FIXTURES TO GRID - IF MANUFACTURES 410.16 CLIPS ARE USED THEY MUST BE EFFECTIVE
5. BOXES MORE THAN 1/4 " 314.20 + OR 1/8 " 314.21
6. WHERE ARE NEW RECEPTACLES AS PER PLANS
7. LABEL CIRCUIT DIRECTORY (408.4) + OUTSIDE COVER
8. FINISH PHASE CONDUCTOR IDENTIFICATION
9. EM LIGHTS NOT WORKING
10. NEW RECEPTACLE BOX OUTSIDE DOOR OVER FILLED
04/19/2012 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*

1. SUPPORT UDV CABLEING 725.8, 800.24, 300.11
2. FILL UNUSED OPENING IN BOXES 110.12
3. USE APPROVED METHODS TO SUPPORT M/C CABLES 330.17 + 330.30, 300.11
4. SECURLY ATTACH FIXTURES TO GRID - IF MANUFACTURES 410.16 CLIPS ARE USED THEY MUST BE EFFECTIVE
5. BOXES MORE THAN 1/4 " 314.20 + OR 1/8 " 314.21
6. WHERE ARE NEW RECEPTACLES AS PER PLANS
7. LABEL CIRCUIT DIRECTORY (408.4) + OUTSIDE COVER
8. FINISH PHASE CONDUCTOR IDENTIFICATION
9. EM LIGHTS NOT WORKING
10. NEW RECEPTACLE BOX OUTSIDE DOOR OVER FILLED
04/19/2012 MECHANICAL - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/19/2012 MECHANICAL - FINAL N/A Not ready for Inspection IVRS - Inspection :*
11/18/2011 ELECTRIC - INTERMEDIATE N/A Partial Approval IVRS - Inspection :*
1) OK WALLS
2) DISCUSSED SERVICE MODIFICATIONS WITH CONTR. TELE/DATA TERM CABINET AND HOSE BIB IN DEDICATED SPACE FOR SERVICE EQUIPMENT MUST BE RELOCATED PER 110.26 NEC

Completed Inspections

Permit Status: Expired
Permit Number: T11CM03278
Permit Description: TI: OFFICE
Total Completed Inspections - 2
Date Description Inspector Results Comments
11/21/2011 FRAMING MHENSON Approved IVRS - Inspection :*
11/30/2011 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
1) SHEETROCK OK

Documents

File Name Document Type  
001_A1.0.TIF CONSTRPLANS VIEW
002_A1.1.TIF CONSTRPLANS VIEW
003_MP1.1.TIF CONSTRPLANS VIEW
004_MP2.1.TIF CONSTRPLANS VIEW
005_MP3.1.TIF CONSTRPLANS VIEW
006_E0.0.TIF CONSTRPLANS VIEW
007_E1.0.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW