Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT UDV CABLEING 725.8, 800.24, 300.11 2. FILL UNUSED OPENING IN BOXES 110.12 3. USE APPROVED METHODS TO SUPPORT M/C CABLES 330.17 + 330.30, 300.11 4. SECURLY ATTACH FIXTURES TO GRID - IF MANUFACTURES 410.16 CLIPS ARE USED THEY MUST BE EFFECTIVE 5. BOXES MORE THAN 1/4 " 314.20 + OR 1/8 " 314.21 6. WHERE ARE NEW RECEPTACLES AS PER PLANS 7. LABEL CIRCUIT DIRECTORY (408.4) + OUTSIDE COVER 8. FINISH PHASE CONDUCTOR IDENTIFICATION 9. EM LIGHTS NOT WORKING 10. NEW RECEPTACLE BOX OUTSIDE DOOR OVER FILLED |
|
| 11/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 2) DISCUSSED SERVICE MODIFICATIONS WITH CONTR. TELE/DATA TERM CABINET AND HOSE BIB IN DEDICATED SPACE FOR SERVICE EQUIPMENT MUST BE RELOCATED PER 110.26 NEC |