Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
122 N CRAYCROFT RD 05
Apply Date:
07/12/2011
Applicant:
N/A
Description:
TI:REPLACE EVAP COOLERS WITH A/C
Contractors:
  • TUHAVI CORPORATION

Permit Reviews

Permit Number - T11CM02210
Permit Status: Final
Permit Description: TI:REPLACE EVAP COOLERS WITH A/C
Start Date Submittal Complete Date Status  
07/12/2011 COMMERCIAL - TI 07/15/2011 ACTIVE Review Details

Outstanding Activity Conditions

Permit Number - T11CM02210
Permit Status: Final
Permit Description: TI:REPLACE EVAP COOLERS WITH A/C
Total Outstanding Activity Conditions - 1
Date Name
07/12/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T11CM02210
Permit Description: TI:REPLACE EVAP COOLERS WITH A/C
Total Completed Inspections - 5
Date Description Inspector Results Comments
08/16/2011 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
08/16/2011 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
1) INCREASE CONDENSATE TO 1" AT THE 1ST TEE
2) EXTEND VENTS IN DRAIN LINES ABOVE DRAIN PANS
3) USE A 1" 90 DEGREE ELBOW AT CONDENSATE TERMINATION
4) FOR FINAL I.D. AIR HANDLER AND CONDENSORS
5) PROVIDE ACCESS TO THE ROOF
6) PROVIDE AIR BALANCE REPORT
08/18/2011 ELECTRIC - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
09/07/2011 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
09/07/2011 ELECTRIC - FINAL JMILITEL Approved IVRS - Inspection :*

Documents

File Name Document Type  
001_C-1.TIF CONSTRPLANS VIEW
002_M-1.TIF CONSTRPLANS VIEW
003_M-2.TIF CONSTRPLANS VIEW
004_E-1.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW