Permit: T11CM01854
Permit Details
Apply Date:
06/13/2011
Applicant:
EASY ENERGY L L C
Description:
ADDITION:SOLAR HOT WATER HEATER
Contractors:
- EASY ENERGY L L C
Permit Reviews
Permit Number - T11CM01854
Permit Status: Final
Permit Description: ADDITION:SOLAR HOT WATER HEATER
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/21/2012 | REVISION - - 3RD | 02/21/2012 | COMPLETED |
| 06/13/2011 | COMMERCIAL - TI | 07/25/2011 | COMPLETED |
| 07/25/2011 | RESUBMITTAL | 07/25/2011 | COMPLETED |
| 08/09/2012 | REVISION - - 4TH | 08/09/2012 | COMPLETED |
| 12/09/2011 | REVISION - - 1ST | 12/09/2011 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T11CM01854
Permit Status: Final
Permit Description: ADDITION:SOLAR HOT WATER HEATER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/13/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T11CM01854
Permit Description: ADDITION:SOLAR HOT WATER HEATER
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2011 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* 1) CU COVERED WITHOUT INSPECTION |
| 12/16/2011 | PLUMBING - FINAL | BBENEDON | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) CAP DRAIN DOWN VALVES, REMOVE HANDLES 2) SUPPORT AND SECURE PIPING AT CONNECTION TO TANK 3) SECURE STRUTS TO PADS 4) SUPPORTS NOT TO EXCEED 8' 5) PROVIDE APPROVED SUPPORTS OVER HEAD IN BOILER ROOM 6) INSULATE COLLECTORS PER YOUR APPROVED PLAN OR REVISE 7) EXPANSION TANK NOT SIZED PER PLAN 8) DID NOT ACCESS ROOF |
| 08/23/2012 | BUILDING - FINAL | DWALKER | Approved | IVRS - Inspection :* |