Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2012 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/15/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE THE WORK 2) PROVIDE A REVISED DETAIL FOR PANEL ATTACHMENT |
|
| 12/16/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAP DRAIN DOWN VALVES, REMOVE HANDLES 2) SUPPORT AND SECURE PIPING AT CONNECTION TO TANK 3) SECURE STRUTS TO PADS 4) SUPPORTS NOT TO EXCEED 8' 5) PROVIDE APPROVED SUPPORTS OVER HEAD IN BOILER ROOM 6) INSULATE COLLECTORS PER YOUR APPROVED PLAN OR REVISE 7) EXPANSION TANK NOT SIZED PER PLAN 8) DID NOT ACCESS ROOF |