Permit: T11BU01586
Permit Details
Apply Date:
12/01/2011
Applicant:
ADOBE FIRE EQUIPMENT INC ,
Description:
KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Contractors:
- ADOBE FIRE EQUIPMENT INC ,
Permit Reviews
Permit Number - T11BU01586
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/01/2011 | MECHANICAL | 12/02/2011 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T11BU01586
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/01/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T11BU01586
Permite Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2012 | FIRE - KITCHEN EXH HOOD FINAL | N/A | Denied | Need 8 ½ inch from center of tanks on the 6 gal Ansul systems All wire connections shall be done outside of the control boxes on the Ansul systems All hood systems shall stay on when the extinguisher system has gone off. Label hoods and pull stations. |