Permit: T11BU01586

Parcel: 12801013B


Addresses:

330 S WILMOT RD

Inspection Status: Denied

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
01/19/2012 FIRE - KITCHEN EXH HOOD FINAL Denied Need 8 ½ inch from center of tanks on the 6 gal Ansul systems
All wire connections shall be done outside of the control boxes on the Ansul systems
All hood systems shall stay on when the extinguisher system has gone off.
Label hoods and pull stations.