Permit: T11BU01215
Permit Details
Apply Date:
09/22/2011
Applicant:
MULTIFAMILY BUILDING SPECIALISTS INC
Description:
INSTALL 1014' OF 4" UNDERGROUND PIPE
Contractors:
- MULTIFAMILY BUILDING SPECIALISTS INC
Outstanding Activity Conditions
Permit Number - T11BU01215
Permit Status: Final
Permit Description: INSTALL 1014' OF 4" UNDERGROUND PIPE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/22/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T11BU01215
Permit Description: INSTALL 1014' OF 4" UNDERGROUND PIPE
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2011 | FIRE SPKLR - UG, PIPING, HYDRO | CSCHULTZ | Approved | 200 PSI FOR 2 HOURS DONE |
12/01/2011 | FIRE SPKLR - UG PIPING FLUSH | CSCHULTZ | Approved | Flushed piping for buildings 1,2,3,4,5,6,7,8,9,10,11,12,13,&24. Piping for Building 17 & 18 was not flushed out piping is still buried underground and capped off not coming out of ground until Phase 2 starts. All fire hydrants are up and working okay to for building in all areas. |
12/01/2011 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | Flushed piping for buildings 1,2,3,4,5,6,7,8,9,10,11,12,13,&24. Piping for Building 17 & 18 was not flushed out piping is still buried underground and capped off not coming out of ground until Phase 2 starts. All fire hydrants are up and working okay to for building in all areas. |