Permit: T11BU01126
Permit Details
Apply Date:
08/30/2011
Applicant:
MULTIFAMILY BUILDING SPECIALISTS INC
Description:
INSTALL 400 LF OF 4 INCH FIRE UNDERGROUND.
Contractors:
- MULTIFAMILY BUILDING SPECIALISTS INC
Outstanding Activity Conditions
Permit Number - T11BU01126
Permit Status: Final
Permit Description: INSTALL 400 LF OF 4 INCH FIRE UNDERGROUND.
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/30/2011 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T11BU01126
Permit Description: INSTALL 400 LF OF 4 INCH FIRE UNDERGROUND.
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2011 | FIRE SPKLR - UG, PIPING, HYDRO | CSCHULTZ | Approved | 200 PSI for 2 hours done all buildings passed |
| 10/05/2011 | FIRE SPKLR - UG PIPING FLUSH | CSCHULTZ | Approved | All buildings are flushed out for 1 to 2 mins. |
| 10/12/2011 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | Still need as builts. Final tie in made all three hydrants flushed, okay to build on all pads. |