Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 10/04/2011 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Approved |
200 PSI for 2 hours done all buildings passed |
| 10/03/2011 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Partial Approval |
Buildings 4-5-6-9-10 site okay to bury. Still needs 200 PSI for 2 hours and flush |
| 09/29/2011 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Partial Approval |
Building #8 and Rec. center okay to bury site only. Still need to do 200 psi for 2 hours and flush. |
| 09/27/2011 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Partial Approval |
Building #2 and #3 ONLY site okay to bury. Still needs 200 PSI for 2 hours and flush. |
| 09/16/2011 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Partial Approval |
Building # 7 ONLY site okay to bury. Still needs 200 psi for 2hours and flush. |
| 09/14/2011 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Partial Approval |
Fire line to Building 1 site check approved. Ok to bury. Still need to do Hydro test and flush. |