Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
9674 E 3RD ST
Address NEW:
9674 E 3RD ST
Apply Date:
05/18/2011
Applicant:
INTEGRITY FIRE PROTECTION L L C
Description:
Install 20 fire sprinklers
Contractors:
  • INTEGRITY FIRE PROTECTION L L C

Outstanding Activity Conditions

Permit Number - T11BU00669
Permit Status: Final
Permit Description: Install 20 fire sprinklers
Total Outstanding Activity Conditions - 1
Date Name
05/18/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T11BU00669
Permit Description: Install 20 fire sprinklers
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/08/2011 FIRE SPKLR - FINAL CSCHULTZ Approved Closet end of hallway (old heater room) over 3 feet wide need sprinkler coverage added.
Northeast bedroom head to far off wall 9' 3" needs to be 9' or less.
Hall bathroom head block by wall to bathtub and toilet correct coverage.
Need lock out on breaker for sprinkler bell
Hydraulic cals don't work static - 59 res - 43
Need to insulate all 1 inch piping in attic
12/08/2011 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved Closet end of hallway (old heater room) over 3 feet wide need sprinkler coverage added.
Northeast bedroom head to far off wall 9' 3" needs to be 9' or less.
Hall bathroom head block by wall to bathtub and toilet correct coverage.
Need lock out on breaker for sprinkler bell
Hydraulic cals don't work static - 59 res - 43
Need to insulate all 1 inch piping in attic
03/06/2012 PERMIT FINALED WMOTTO Approved