Permit: T11BU00669

Parcel: 133411060


Addresses:

9674 E 3RD ST

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
03/06/2012 FIRE SPKLR - OH PIPING & HYDRO Approved
12/08/2011 FIRE SPKLR - OH PIPING & HYDRO Denied Closet end of hallway (old heater room) over 3 feet wide need sprinkler coverage added.
Northeast bedroom head to far off wall 9' 3" needs to be 9' or less.
Hall bathroom head block by wall to bathtub and toilet correct coverage.
Need lock out on breaker for sprinkler bell
Hydraulic cals don't work static - 59 res - 43
Need to insulate all 1 inch piping in attic