Permit: T10PL01932
Permit Details
Apply Date:
12/14/2010
Applicant:
CARRANZA LUIS A & DORA P JT/RS
Description:
RECONNECT:GAS RES
Outstanding Activity Conditions
Permit Number - T10PL01932
Permit Status: Expired
Permit Description: RECONNECT:GAS RES
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/14/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10PL01932
Permite Description: RECONNECT:GAS RES
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2010 | PLUMBING - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SEDIMENT TRAP AT WATER HEATER 2) WATER HEATER FLUE PIPE NOT SCREWED, PROVIDE MINIMUM 3 SCREWS PER JOINT 3) HEATER COMBUSTION AIR IS RESTRICTED, PROVIDE FREE AIR SPACE OF 1 SQUARE INCHE PER 1000 BTU'S 4) PROVIDE SEDIMENT TRAP AT GAS LINE TO HEATER 5) EXPOSE BURRIED GAS PIPE FOR INSPECTION 6) NOTE: THIS IS NOT A SIMPLE GAS RECONNECT, THERE IS A NEW BURRIAL LINE FROM METER TO ? |