Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
Permit Number - T10PL01932
Inspection Description - PLUMBING - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SEDIMENT TRAP AT WATER HEATER 2) WATER HEATER FLUE PIPE NOT SCREWED, PROVIDE MINIMUM 3 SCREWS PER JOINT 3) HEATER COMBUSTION AIR IS RESTRICTED, PROVIDE FREE AIR SPACE OF 1 SQUARE INCHE PER 1000 BTU'S 4) PROVIDE SEDIMENT TRAP AT GAS LINE TO HEATER 5) EXPOSE BURRIED GAS PIPE FOR INSPECTION 6) NOTE: THIS IS NOT A SIMPLE GAS RECONNECT, THERE IS A NEW BURRIAL LINE FROM METER TO ? |