Permit Details

Status:
C of o
Type:
COMMERCIAL OTHER
Address:
244 S TUCSON BL
Apply Date:
10/12/2010
Applicant:
CARL WELLS
Description:
C OF O: GYM/TRAINING FACILITY

Permit Reviews

Permit Number - T10OT02201
Permit Status: C of o
Permit Description: C OF O: GYM/TRAINING FACILITY
Start Date Submittal Complete Date Status  
10/12/2010 C OF O 10/29/2010 COMPLETED Review Details

Completed Inspections

Permit Status: C of o
Permit Number: T10OT02201
Permit Description: C OF O: GYM/TRAINING FACILITY
Total Completed Inspections - 3
Date Description Inspector Results Comments
11/02/2010 CERTIFICATE OF OCCUPANCY MHENSON Approved IVRS - Inspection :*
1) BACKFLOW PREVENTERS ON HOSE BIBS
2) NO OPEN JUNCTION BOXES PLUG UNUSED KNOCKOUTS AND MISSING COVER PLATES
3) REMOVE STAIRS TO KNOW WHERE
4) LOFT NEEDS GUARD RAIL 42"-4" SPHERE CANNOT PASS THRU OPENINGS
5) LABEL ALL CIRCUIT BREAKERS (3 PANELS)
6) LABEL EXIT (SIGNS)
7) STEP AT NORTH EXIT
8) UNIX RESTROOM, NO KNOWLEDGE LEVER KNOB SPLIT FRONT TOILET SEAT, SIGNAGE ON OTHER RESTROOMS
9) INSTALL 15" ADDRESS
10) DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS SIGNS AND REMOVE INTERIOR KEYED DEAD BOLTS
11) NEED FIRE C OF O
11/02/2010 FIRE - FINAL DRamirez Approved Not approved 11/2/10
1.) Need illuminated exit signs for both of the required exit doors.
2.) Need "emergency back-up" lighting for both of the required exit doors.
3.) Replace all missing cover plates.
4.) The "loft" area must be secured with safety railing or must eliminate the access.
5.) Provide a "step" for the landing area outside the exterior on the north wall.
6.) The secondary doors located next to the rear exit door must open in the direction of egress travel.
7.) Must provide a "step" for the landing area out side the two doors located next to the rear exit door.
8.) Remove the keyed lock from the front,west door and replace with a thumb-turn lock.
9.) The double-doors located next to the stairs in the area under the loft must open in the direction of egress travel and must open simultaneously.
10.) Secure all "ROMEX" wiring that is installed below 7 feet and located in the furnace room. Must be in conduit or behind drywall.
11.) Dry-wall the ceilng in the furnace room to prevent smoke and fire from traveling to other parts of the building.
12.) Need a sign over the main door reading, "DOOR MUST REMAIN UNLCKED WHEN THE BUILDING IS OCCUPIED".
11/03/2010 ZONING - FINAL DROBERTS Approved SITE WAS CHECKED DURING THE INITIAL INSPECTION AND APPEARED TO NOT BE COMPLETE ENOUGH FOR THE FINAL RELEASE OF THE C OF O.
I MET WITH THE TENANT AND LOOKED AT THE INFORMATION THAT WAS PROVIDED BY THE ZONING SECTION DURING THE PLAN APPROVAL PROCESS. HE HAD A COPY OF THE AERIAL PICTURE FOR THIS SITE PLUS A SIGNED AFFIDAVID FROM THE OWNER STATING THAT THE SITE HAD NOT CHANGED THE SITE CONDITIONS SINCE THE 2005 AERIALS. THERE WAS NO STRIPING IN THE PARKING AREA, BUT THERE WERE PARKING BLOCKS FOR EACH OF THE LOCATIONS FOR THIS SITE. A PARTIAL WAS GIVEN AT THIS TIME UNTIL THE REQUIREMENTS FOR THE SITE COULD BE VERIFIED BY THE ZONING DEPARTMENT.
I MET WITH DAVID RIVERA TO DISCUSS WHAT TYPE OF INSPECTION THIS WAS AND HOW IT WAS TO BE DONE. HE SHOWED ME THE REQUIREMENTS FOR ORDINANCE #10835 AND ADVISED ME ABOUT WHAT ITEMS TO LOOK FOR DURING THIS INSPECTION, AND ONLY THESE ITEMS UNLESS SOMETHING ELSE WAS A HEALTH AND SAFETY ISSUE. A RE-INSPECTION OF THIS SITE WAS PERFORMED AT THE END OF THE DAY AND APPROVED AT THAT TIME, THE CONDITIONS HAVE BEEN MET AND THERE DOES NOT APPEAR TO BE A HEALTH AND SAFETY ISSUE.

I HAVE ASKED JIM FEMLING AND DAVID RIVERA TO HAVE THIS AS A TOPIC OF DISCUSSION IN OUR NEXT WEEKLY MEETING SO THAT WE CAN HAVE A FULL UNDERSTANDING ABOUT WHAT IS TO BE INSPECTED SO THAT THEY ARE NOT DENIED FOR REASONS THAT DO NOT APPLY TO THE SITE. IT IS ALSO UNSURE AT THIS TIME WHO WILL BE THE INSPECTOR THAT WILL BE REVIEWING THESE IN THE FIELD, IT MAY BE ENGINEERING, BUILDING FINAL, OR THE ACTUAL ZONING REVIEWER THAT WILL MAKE THESE FIELD DECISIONS.