Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10OT02201

Parcel: 12901035E


Addresses:

244 S TUCSON BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T10OT02201

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/16/2011 FIRE - FINAL Approved
11/02/2010 FIRE - FINAL Denied Not approved 11/2/10
1.) Need illuminated exit signs for both of the required exit doors.
2.) Need "emergency back-up" lighting for both of the required exit doors.
3.) Replace all missing cover plates.
4.) The "loft" area must be secured with safety railing or must eliminate the access.
5.) Provide a "step" for the landing area outside the exterior on the north wall.
6.) The secondary doors located next to the rear exit door must open in the direction of egress travel.
7.) Must provide a "step" for the landing area out side the two doors located next to the rear exit door.
8.) Remove the keyed lock from the front,west door and replace with a thumb-turn lock.
9.) The double-doors located next to the stairs in the area under the loft must open in the direction of egress travel and must open simultaneously.
10.) Secure all "ROMEX" wiring that is installed below 7 feet and located in the furnace room. Must be in conduit or behind drywall.
11.) Dry-wall the ceilng in the furnace room to prevent smoke and fire from traveling to other parts of the building.
12.) Need a sign over the main door reading, "DOOR MUST REMAIN UNLCKED WHEN THE BUILDING IS OCCUPIED".