Description:
C OF O: CHURCH

Permit Reviews

Permit Number - T10OT02171
Permit Status: Expired
Permit Description: C OF O: CHURCH
Start Date Submittal Complete Date Status  
10/06/2010 C OF O 10/06/2010 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T10OT02171
Permite Description: C OF O: CHURCH
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
01/06/2011 CERTIFICATE OF OCCUPANCY N/A Not ready for Inspection IVRS - Inspection :*
1) 1 HR RATED CORRIDOR NEEDS RATED DOORS INSTALLED
2) NEED MECH INSPECTOR TO INSPECT KITCHEN RANGES AND HOOD
3) NEED FIRE C OF O APPROVED AND THEIR CORRECTIONS MADE
01/06/2011 FIRE - FINAL N/A Denied Not approved 01/06/11
1.) Address numbers for the building must be at least 12 inches tall with a contrasting background and must be readily visible from street.
2.) Need a sign over double swinging doors located between the main exit and the foyer area that reads,"DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED".
3.) All portable fire extinguishers in the building need current annual service inspection tag.
4.) All extinghishers must be labled.
5.) All emergency back-up lights are burnt out. Must be funtional at all times.
6.) Must remove the flush-bolt locks from the double swinging doors that lead into the main floor area and into the recreational area.
7.) Must remove the door holders from same set of double doors.
8.) Maintain a clear area around the hot water heater.
9.) Repair/cover or remove the exposed open-end wiring located in water heater room.
10.) Lable main exterior electrical panel, "ELECTRICAL" or "ELECTRICAL PANEL".
11.) All doors in the rated exit corridor must also be 1hr. rated and sealed.
12.) Need a knox-box for the the parking lot gates ( will provide knox-box order form)
13.) Need a sign over the main door (rear building) reading,"DOOR MUST REMAIN UNLOCKED ............ OCCUPIED"
14.) Remove the keyed turn lock from rear door (rear building) and replace with a thumb-turn lock.