Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
2532 E 6TH ST
Apply Date:
08/27/2010
Applicant:
MARIANNA LEONARAI
Description:
C OF O:SALES/RETAIL

Permit Reviews

Permit Number - T10OT01852
Permit Status: Expired
Permit Description: C OF O:SALES/RETAIL
Start Date Submittal Complete Date Status  
08/27/2010 C OF O 08/30/2010 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T10OT01852
Permite Description: C OF O:SALES/RETAIL
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
09/01/2010 CERTIFICATE OF OCCUPANCY N/A Not ready for Inspection IVRS - Inspection :*
1) REPAIR CEILING IN WEST RESTROOM
2) MAIN ENTRY SIGNAGE "DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS" (3 SIGNS)
3) FIRE ITEMS FOR CORRECTION
5) RESTROOM SIGNS (2)
09/01/2010 FIRE - FINAL N/A Denied Not approved 1/1/10
1.) Need a sign over the three front exit doors reading,"DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED"
2.) Need thumb-turn locks for all secondary exit doors. Remove double-cylinder locks.
3.) Need illuminated exit signs for all front exit doors.
4.) Need illuminated directional exit signs directing the pathway to the front exit doors.
5.) Maintain a clear and unobstructed pathway to all exits at all times.
6.) The west rear double doors are hard to open. Must be readily openable at all times.
7.) Need "NOT AN EXIT" signs over the French doors and over the doors leading to the rear of the building next to the bathrooms.
8.) The portable fire extinguishers need annual servicing.
9.) Storage must have a clearance of at least 18 inches from ceiling.
10.) Need emergency back-up lighting for all three areas leading to the front exit doors.

Documents

File Name Document Type  
None DOCUMENTS VIEW