Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
Permit Number - T10OT01852
Inspection Description - FIRE - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/01/2010 | FIRE - FINAL | Denied | Not approved 1/1/10 1.) Need a sign over the three front exit doors reading,"DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED" 2.) Need thumb-turn locks for all secondary exit doors. Remove double-cylinder locks. 3.) Need illuminated exit signs for all front exit doors. 4.) Need illuminated directional exit signs directing the pathway to the front exit doors. 5.) Maintain a clear and unobstructed pathway to all exits at all times. 6.) The west rear double doors are hard to open. Must be readily openable at all times. 7.) Need "NOT AN EXIT" signs over the French doors and over the doors leading to the rear of the building next to the bathrooms. 8.) The portable fire extinguishers need annual servicing. 9.) Storage must have a clearance of at least 18 inches from ceiling. 10.) Need emergency back-up lighting for all three areas leading to the front exit doors. |