Description:
C OF O: MARTIAL ARTS SCHOOL
Permit Reviews
Permit Number - T10OT01784
Permit Status: Expired
Permit Description: C OF O: MARTIAL ARTS SCHOOL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/20/2010 | C OF O | 08/20/2010 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10OT01784
Permite Description: C OF O: MARTIAL ARTS SCHOOL
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2010 | FIRE - FINAL | N/A | Denied | Not approved 8/24/10 1.) Address numbers must be readily visible from the street. 2.) Front security gate must be LOCKED in the OPEN position at all times when the building is occupied. 3.) Only one lock is allowed per exit door. 4.) Remove the slide-bolt from front door. 5.) Need a sign over the front door and over the security gate that reads, "DOOR MUST REMAI UNLOCKED WHEN BUILDING IS OOCUPIED". 6.) Provide a "NOT AN EXIT " sign for the west rear door. 7.) Need a sign on the exterior side of the rear north door reading , "DOOR BLOCKED'. Minimum of 4-6 inches high. |
Completed Inspections
Permit Status: Expired
Permit Number: T10OT01784
Permit Description: C OF O: MARTIAL ARTS SCHOOL
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2010 | CERTIFICATE OF OCCUPANCY | LHANLY | Approved | NEW STAIRS DO NOT COMPLY WITH IBC. RUN TO BE 11" MINIMUM, HANDRAILS ARE MISSING. PLUMBING REPAIRS OK. |
| 02/25/2011 | CofO - ORDINANCE 10835 | LHANLY | Approved |