Permit: T10OT01023
Permit Details
Apply Date:
05/12/2010
Applicant:
CHAN, CHU
Description:
C/O:RESTAURANT
Permit Reviews
Permit Number - T10OT01023
Permit Status: Expired
Permit Description: C/O:RESTAURANT
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
05/12/2010 | C OF O | 05/12/2010 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10OT01023
Permite Description: C/O:RESTAURANT
Total Outstanding Inspections - 3
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
HEALTH DEPT - FINAL 724-7908 | N/A | Not Inspected | ||
05/13/2010 | CERTIFICATE OF OCCUPANCY | N/A | Not ready for Inspection | IVRS - Inspection :* |
05/13/2010 | FIRE - FINAL | N/A | Denied | 1. Coverage for extinguisher system on hood needs to be checked out not properly covered. 2. All cooking equipment shall be 6 inches inside hood coverage. Need to move 6 burner stove/grill on east end over. 3. Need to clean hood of all grease from roof top to equipment. 4. Occ. Load set for 65 only one exit need two exits opening outward. 5. Floor plans do not reflect what is on site need better plans showing the proper floor plan. |