Permit Reviews

Permit Number - T10OT01023
Permit Status: Expired
Permit Description: C/O:RESTAURANT
Start Date Submittal Complete Date Status  
05/12/2010 C OF O 05/12/2010 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T10OT01023
Permite Description: C/O:RESTAURANT
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
HEALTH DEPT - FINAL 724-7908 N/A Not Inspected
05/13/2010 CERTIFICATE OF OCCUPANCY N/A Not ready for Inspection IVRS - Inspection :*
05/13/2010 FIRE - FINAL N/A Denied 1. Coverage for extinguisher system on hood needs to be checked out not properly covered.
2. All cooking equipment shall be 6 inches inside hood coverage. Need to move 6 burner stove/grill on east end over.
3. Need to clean hood of all grease from roof top to equipment.
4. Occ. Load set for 65 only one exit need two exits opening outward.
5. Floor plans do not reflect what is on site need better plans showing the proper floor plan.